DRYERS SMC - OVERVIEW


IDFA-E / IDF refrigerated air dryer series
  • Start of the art design ensures a constant 3°C pressure dew point.
  • High efficiency heat exchanger.
  • Environmentally ozone friendly R134a and R407C refrigerant.
  • Conforms to stringent ISO8573-1 standards.
SPECIFICATION

   IDFA / IDF Refrigerant:


Refrigerant Air Dryer IDFA Series Small - 3E, 4E, 6E, 8E, 11E, 15E, 22E, 37E, 55E, 75E
Model IDFA3E
-23
IDFA4E
-23
IDFA6E
-23
IDFA8E
-23
IDFA11E
-23
IDFA15E
-23
IDFA22E
-23
IDFA37E
-23
IDFA55E
-23
IDFA75E
-23
Rated
Condition
Air Flow Rate
µ min (ANR) *Note1
283 566 833 1516 1866 2800 4233 6366 8500 13700
At Outlet Pressure Dew Point of 10°C
Operating Pressure(MPa) 0.7
Inlet Air Temparature( °C) 35
Ambient Temparature( °C) 25
Operating
Ranges
Working Fluid Compressed Air
Inlet Air Temparature( °C) 5 to 50
Inlet Air Pressure(MPa) 0.15 to 1.0
Ambient Temperature( °C) 2 to 40 (Relative humidity of 85% or less)
Electrical
Specification
Power Supply Voltage Single Phase 230 VAC ± 10% 50Hz
Operating Current (A) *Note2 1.2 1.2 1.2 1.4 2.7 3.0 4.0 5.4 7.9
Power Consumption (W) *Note2 180 180 180 208 385 470 760 1130 1700
Circuit Breaker (A) *Note3 5 10 20
Condenser Air-cooled type
Refrigerant R134A (HFC) R407C (HFC)
Auto Drain Float type
(normally closed)
Float type (normally open)
Port Size Rc 3/8 Rc 1/2 Rc 3/4 Rc 1 R 1 R 1·1/2 R2
Accessory (kg) Hexagon nipple
Weight (kg) 18 22 23 27 28 46 54 62 100 116
Coating Color Body panel: White 1 Base: Gray 2
Compliant Standards EU directive compliant (with CE marking)
Applicable Compressor kW (Standard) 2.2 3.7 5.5 7.5 11 15 22 37 55 75
*Note1: The data for µmin (ANR) refers to the condition of 20 °C, 1 atm. pressure and relative humidity of 65%.
*Note2: The value is that of under specified condition.
*Note3: Install GFCI breaker that comes with sensivity of 30mA.
*Note4: When short period power shortage (including instantly recovered shortage) is recovered.
It may take a longer starting period the un-usual starting or may not start due to the protective devices.

Refrigerant R22 Series IDF Medium - 11D, 11C, 15C, 15C1, 22C, 22C1, 37C, 37C1, 55C, 75C
Model IDF11D IDF11C IDF15C IDF15C1 IDF22C IDF22C1 IDF37C IDF37C1 IDF55C IDF75C
Rated
Conditions
Air Flow Rate
µ min (ANR) *Note1
50Hz 1300 2050 3150 5200 7650 10500
60Hz - 1500 2400 - - 3700 - 6100 9000 12400
Operating Pressure(MPa) 0.7
Inlet Air Temparature( °C) 40
Ambient Temparature( °C) 32
Pressure Dew Point( °C) 10
Operating
Ranges
Working Fluid Compressed Air
Inlet Air Temparature( °C) 5 to 50
Inlet Air Pressure(MPa) 0.15 to 1.0
Ambient Temperature( °C) 2 to 40 (Relative humidity of 85% or less)
Electrical
Specs
Power Source Single Phase 100/100 to 110VAC(50/60Hz)
220/240VAC(50Hz)
220 to 240VAC(50Hz)
Three Phase,200/200 to 220VAC(50/60Hz)
Single Phase,200,400VAC(50Hz)
Power
Con-
sumption
(W)
100
VAC
50Hz - 320 543 - - - - - - -
60Hz - 347 662 - - - - - - -
200
VAC
50Hz - 308 561 - - 670 - 750 1400 2100
60Hz - 346 652 - - 800 - 880 1750 2150
220
to
240
VAC
50Hz 337 - - - - - - - - -
220
VAC
50Hz - - - 548 747 - 830 - 1530 2150
240
VAC
50Hz - - - 570 777 - 860 - 1580 2200
Circuit Breaker (A) *Note2 10(for 100VAC), 5(for 200VAC) 10 15
Condenser Air Cooled
Refrigerant R134a R22
Air Connection Rc 3/4 Rc 1 Rc 1 1/2 Rc 2
Drain Connection Rc 1/4
Auto Drain INA-20-41-04 *Note3
Weight (kg) 100 to 200VAC - 47 50 - - 60 - 72 114 126
220 to 240VAC 50 - - 53 60 - 72 - 125 135
Coating Color Munsell 10Y8/0.5 (White)
Applicable Compressor (screw type) kW 11 15 22 37 55 75
*Note1: The data for µmin (ANR) refers to the condition of 20 °C, 1 atm. pressure and relative humidity of 65%.
*Note2: Install a circuit breaker with sensitivity of <=30 mA.
*Note3: Spare part for auto drain INA-20-41-04 is AD44-x445.

Accessories (Option)
Description Features Specifications Applicable Dryer Dimensions
Transformer Separately Installed
This is for power and voltage supply other than standard. Max. ambient temparature 40°C (Relative humidity 85% or less) All models 14-17-30
Base Integrated with Transformer
Avoid decreasing of air dryer performance even in dusty atmosphere. IDU3D to 15C
IDF4D to 75C
14-17-30
Dust Proof Filter Set
This is the base for integrating the transformer and air dryer. Max. ambient temparature 40°C IDU3D to 75C
IDF1D to 75C
14-17-30
Bypass Piping Set
Easy bypass piping (connect this set to air dryer), realizing substantial reduction of man-hours at the site. Max. operating pressure 1.0MPa
Max. operating temperature 60°C
IDU3D to 75C
IDF1D to 75C
14-17-31